Page 1 of 2 ADDENDUM NO. 2 TO TERMINAL EXPANSION AIP 3-31-0045-036 (CARES) At KEARNEY REGIONAL AIRPORT (EAR) KEARNEY, NE Addendum Date: August 30, 2022 To Prospective Bidders: The contract documents/specifications and plans for the above referenced project are hereby amended as follows: Specifications: Entry 1: Appendix 2 Section 044310 - NATURAL THIN STONE, Section 2.4 - ACCESSORIES, item D Drainage Mat: Subject to compliance with the specifications, add the following to the list of approved manufacturers. - ClarkDietrich E-Screen Rain Screen (888) 437-3244 www.clarkdietrich.com Entry 2: Appendix 2 Section 087100 – DOOR HARDWARE, In the Hardware Sets section, Set: 12.0, add door number E104A Entry 3: Appendix 2 Section 145400 – BAGGAGE HANDLING SYSTEMS, Section 1.1 SUPPLIERS: Subject to compliance with the specifications, add the following as approved manufacturers. - Five Star Airport Alliance Address: 1630
S 4800 W, Suite D, Salt Lake City, UT 84104 Contact: Justin Lowder Phone: (801) 430-6025 Entry 4: Appendix 2 Section 271500 – COMMUNICATION CABLING SYSTEMS, Section 2.4 STRUCTURED CABLING SOLUTION: Subject to compliance with the specifications, add the following as approved manufacturers. d. Siemon Co. (Premium 6 series cable) d. Siemon Co. (Premium 6A series cable) Entry 5: Appendix 2 Section 270528 – LOW VOLTAGE CONDUIT SYSTEM, Section 2.1 EQUIPMENT FURNISHED: Remove the following verbiage “under alternate bid” from items A, B, and C. Plans: Entry 6: Plan Sheet Drawing No. A12.0: At Equipment Schedule Item #1, at ‘Description’ add the following text: “SIZE APPROXIMATELY 24’-0”L x 11’-0”W x 30”D, FIELD VERIFY ALL DIMENSIONS.” Page 2 of 2 Entry 7: Plan Sheet Drawing No. A12.0: At Furniture, Fixtures and Equipment General Notes, add the following note: “8. PALLET LOOP BAGGAGE CLAIM CAROUSEL TO INCLUDE TUG SIDE GUARD RAIL, INFILL AT CLAIM DEVICE, PUBLIC SIDE STAINLESS STEEL FINISH, AND STAINLESS STEEL TRIM AT FIRE/SECURITY DOORS.” Entry 8: Plan Sheet Drawing No. A12.0: At Equipment Schedule Item #11, replace content in ‘Description’ column to read: “EXISTING MANUAL GRAVITY ROLLERS” in lieu of “2 DEG. SLOPED GRAVITY ROLLERS WITH STEEL RAIL.” Entry 9: Plan Sheet Drawing No. A12.0: At Equipment Schedule Item #11, replace content in ‘Type Comments’ column to read: “N.I.C. – TSA INSTALLED” in lieu of “CONTRACTOR PROVIDED AND INSTALLED.” Entry 10: Plan Sheet Drawing No. S2.1: Modified Note 3 for Roof Framing Plan to include the stud bearing symbol. See revcloud on reissued plan S2.1 sheet attached (Attachment No. 1) to this addendum. Entry 11: Plan Sheet Drawing No. E0.0: At GENERAL SPECIAL SYSTEMS NOTES section, Revise Note 2. to read as follows: “SPECIAL SYSTEMS ROUGH-INS PROVIDED BY ELECTRICAL CONTRACTOR.” In lieu of “SPECIAL SYSTEMS ROUGH-INS PROVIDED BY ELECTRICAL CONTRACTOR UNDER BASE BID. UNDER ALTERNATE BIDS PROVIDE COMPLETE TELECOMMUNICATIONS, SECURITY, AND AUDIO-VISUAL SYSTEMS.” Entry 12: Plan Sheet Drawing No. E6.1: Revise luminaire schedule acceptable manufacturers. See revcloud on reissued plan E6.1 sheet attached (Attachment No. 2) to this addendum. Other: Entry 13: Attached to this addendum is the current plan holders list (as of August 30, 2022) for reference (Attachment No. 3). END OF CHANGES PER ADDENDUM NO. 2 Prepared by: Alfred Benesch & Company Signature of Preparer: _________________ 825 “M” Street, Suite 100 Lincoln, NE 68508 (402) 479-2200 FAX: (402) 479-2276 TERMINAL EXPANSION KEARNEY REGIONAL AIRPORT (EAR) KEARNEY, NEBRASKA AIP 3-31-0045-036 (CARES) ADDENDUM NO. 2 ATTACHMENT NO. 1 Revised Plan Sheet Drawing S2.1 NOTES 1. 2. 3. 4. 5. REFER TO DESIGN DATA, SCHEDULES & TYP DETAILS INDICATES SHEET NOTE REFER TO PLAN FOR LOCATION TOF = 99'-4" UNLESS NOTED OTHERWISE COLUMN SCHEDULE GUIDE C-X COLUMN MARK BP-X BASE PLATE MARK F-X FOOTING MARK XX'-X TOP OF FOOTING INDICATES HOLDDOWN SIMPSON HDU2-SDS2.5 UNLESS NOTED OTHERWISE 4" CONCRETE ON PROPERLY PREPARED GRANULAR FILL & SUBGRADE REFER TO SOILS REPORT. REINFORCE w/ 6x6-W1.4xW1.4 WWF. REFER TO ARCH FOR VAPOR BARRIER. 6 # DOWEL FOOTING REINF INTO EXISTING FND DRILL & ADHERE w/ HILTI HIT-HY 200 w/ 9" EMBED DRILL VERTICAL DOWELS 3" INTO STOOP SLAB ADHERE w/ HILTI HIT-HY 200 ALL EXTERIOR WALLS ARE CONSIDERED SHEAR WALLS, ADDITIONALLY ALL WALLS BETWEEN HOLD DOWNS (INDICATED BY MARK SW) SAWCUT NOTCH IN EXISTING FOOTING FOR RESTROOM PLUMBING, NOT TO EXCEED 8"x8"x8" IN SIZE. 7 8 9. 10 1 EX. 5 EX. 5 EX. 4 EX. 4 EX. 3 EX. 3 EX. 2 EX. 2 10'-8" 7'-10" EX. A EX. B EX. C EX. D EX. EEX. B.9 EX. D.2 2 5 '- 1 0 3 /8 " 2 6 '- 4 " 2 7 '- 9 1 /4 " 2 0 '- 0 3 /8 " 2 5 '- 9 1 /8 " 1 9 '- 1 1 /2 " 73'-7 3/4" 5'-10 1/8" 18'-5 5/8" 2'-0" 23'-0" 5'-6 3/8" 18'-5 5/8" 4" EX. E.1 EX. F C C B 3 3 EX. 1 EX. 1 2 2 1 A 4 7 '- 9 5 /8 " 5 7 /8 " 2 2 '- 9 1 /4 " 2 '- 6 " 1 9 '- 1 1 /2 " CF-1 C F -1 CF-2 CF-2 CF-1 C F -2 C F -2 CF-2 C F -1 C F -1 CF-1 C F -2 HDU4-SDS2.5 HDU4-SDS2.5 21 S3.1 20 S3.1 21 S3.1 21 S3.1 21 S3.1 20 S3.1 20 S3.1 20 S3.1 20 S3.1 18 S3.1 18 S3.1 19 S3.1 19 S3.1 1.9 1.9 1 4 '- 0 1 /4 " 3'-11 3/8" HSS5X5X1/4 BP-1 F-1 35'-6" 49'-0" 84'-6" 1 0 0 '- 0 " 4 4 '- 1 0 5 /8 " 2 3 '- 3 1 /8 " 2 '- 6 " F-10 1 3 '- 3 1 1 /1 6 " 16 S3.1 17 S3.1 SIM 7 7 7 6 FINISH FLOOR = 100'-0 6 6 6 '- 9 " 2 '- 3 " 3 " 4 '- 6 " 7 '- 0 " 9'-0" 3" 2 1 /2 " 1 3 '- 9 1 /2 " B.8 8'-10 1/4" CF-10 3'-6" 1 1/2" 22 S3.1 22 S3.1 7 8 7 SW S W SW S W S W SW S W S W SW 10 1 1 1 1 1 1 1 1 1 1 EX. 5 EX. 5 EX. 4 EX. 4 EX. 3 EX. 3 EX. 2 EX. 2 EX. A EX. B EX. C EX. D EX. EEX. B.9 EX. D.2 2 5 '- 1 0 3 /8 " 2 6 '- 4 " 2 7 '- 9 1 /4 " 2 0 '- 0 3 /8 " 2 5 '- 9 1 /8 " 1 9 '- 1 1 /2 " 97'-3 7/8" 5'-10 1/8" 18'-5 5/8" 2'-0" 23'-0" 5'-6 3/8" 18'-5 5/8" 24'-0 1/8" FV 18'-0" FV 12'-6 3/8" EX. E.1 EX. F C C B 3 3 EX. 1 EX. 1 2 2 1 A 35'-6" 49'-0" 4" 4 7 '- 9 5 /8 " 5 7 /8 " 2 2 '- 9 1 /4 " 2 '- 6 " 1 9 '- 1 1 /2 " 11 7/8" TJI 560 11 7/8" TJI 360 @ 16" OC 11 7/8" TJI 360 @ 16" OC 11 7/8" TJI 210 11 7/8" TJI 110 @ 16" OC 11 7/8" TJI 110 @ 16" OC 1 1 7 /8 " T J I 1 1 0 @ 1 6 " O C 3- 1 3/4"x9 1/2" LVL 2 5 S3.1 5 S3.1 5 S3.1 4 S3.1 4 S3.1 3 S3.1 3 S3.1 3 S3.1 3 S3.1 3 S3.1 2 1.9 1.9 11 S3.1 8 S3.1 3 S3.1 2- 1 3/4"x11 7/8" LVL 2- 1 3/4"x11 7/8" LVL 1 1 7 /8 " T J I 1 1 0 @ 1 6 " O C 1 1 7 /8 " T J I 1 1 0 @ 1 6 " O C 3 - 1 3 /4 "x 1 4 " L V L 3 3 13 S3.1 14 S3.1 12 S3.1 12 S3.1 15 S3.1 10 S3.1 1 S3.1 2 - 1 3 /4 "x 1 1 1 /4 " L V L 2 - 1 3 /4 "x 1 1 1 /4 " L V L 7 S3.1 2 2 2 2 1 3/4x9 1/4" @ 16" OC D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T 2- 1 3/4"x11 7/8" LVL 2 2 3- 2x12 2 2 D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T D O U B L E J O IS T L-3 L -1 L -3 L-3 84'-6" 1 0 0 '- 0 " 4 4 '- 1 0 5 /8 " 2 3 '- 3 1 /8 " 2 '- 6 " L -3 L-2 L -3 3- 2x12 L-3 2- 2x12 1 1 2 S3.1 B.8 1 3 /4 x 1 1 1 /4 " 5 5 6 9" 2'-3" 1'-0" T O P O F P A R A P E T = 1 1 3 '- 6 T O P O F P A R A P E T = 1 1 3 '- 6 TOP OF PARAPET = 113'-6 TOP OF PARAPET = 113'-6 T O P O F P A R A P E T = 1 1 3 '- 6 TOP OF SHEATHING = 111'-6 W8x18 W8x10 W8x10 W8x10 7 7 7 7 8'-10 1/4" 3 9 S3.1 6 S3.1 NOTES 1. 2. 3. 4. REFER TO DESIGN DATA, SCHEDULES & TYP DETAILS UNLESS NOTED OTHERWISE ALL DIMENSIONS ARE TO FACE OF WALL FRAMING OR CENTERLINE OF COLUMNS INDICATES REQUIRED NUMBER OF BEARINGS STUDS INDICATES SHEET NOTE REFER TO PLAN FOR LOCATION SISTER 2x12 TO EXISTING JOIST, ATTACH TO EXISTING JOIST w/ 3- .148"x3" NAIL @ 12" OC REMOVE 2- 2x12 JOIST REPLACE w/ 2x12 JOIST AS INDICATED 5 # 6 POCKET BEAM INTO EXISTING WALL. BEAR BEAM MIN 4" ON 3/8x6x8" EMBED PL w/ 2- 1/2"x6" HS, WELD TO EMBED w/ 3/16"x3" FILLET EA SIDE 7 # 2 7/2 9/2 022 SHEET NO. DATE PROJECT KEARNEY TERMINAL SEAL NO . RE VI SI ON S DA TE CIVIL ENGINEER DR AW N BY : DE SI GN ED BY : RE VI EW ED BY : QU AN TI TI ES CH EC KE D BY : ARCHITECT CONSULTANT K E A R N E Y R E G IO N A L A IR P O R T T E R M IN A L E X P A N S IO N K E A R N E Y , N E B R A S K A 1 AD DE ND UM 1 08 -2 4- 22 2 AD DE ND UM 2 08 -3 0- 22 7/29/2022 S2.1 ST RU CT UR AL P LA NS 1/8" = 1'-0" 1 FOUNDATION PLAN 1/8" = 1'-0" 2 ROOF FRAMING TERMINAL EXPANSION KEARNEY REGIONAL AIRPORT (EAR) KEARNEY, NEBRASKA AIP 3-31-0045-036 (CARES) ADDENDUM NO. 2 ATTACHMENT NO. 2 Revised Plan Sheet Drawing E6.1 GENERAL REQUIREMENTS: A. CONTRACTOR SHALL VERIFY CATALOG NUMBERS AND INSTALLATION REQUIREMENTS PRIOR TO ORDERING. NOTIFY ENGINEER OF ANY CONFLICTS WITH PROPOSED INSTALLATION. B. ALL LUMINAIRES SHALL BE 'BUY AMERICA' COMPLIANT. LUMINAIRE SCHEDULE NOTES: 1. LUMINAIRE SHALL BE CONSIDERED EQUAL AS MANUFACTURED BY: ACUITY BRANDS, HUBBELL, COOPER, OR PHILIPS LIGHTING. 2. LUMINAIRE SHALL BE CONSIDERED EQUAL AS MANUFACTURED BY: GOTHAM, PATHWAY, PRESCOLITE, OR COOPER PORTFOLIO. 3. REFER TO PLANS FOR MOUNTING REQUIREMENTS SUCH AS WALL MOUNT, END MOUNT, CEILING MOUNT AND PROVIDE LUMINAIRES ACCORDINGLY. PROVIDE DIRECTIONAL CHEVRON ARROWS AS INDICATED ON PLANS. 4. REFER TO PLANS FOR RUN LENGTHS AND CONFIGURATIONS REQUIRED. LUMINAIRE SHALL BE CONTINUOUS FOR ENTIRE LENGTHS OF WALLS. PRIOR TO ORDERING CONTRACTOR SHALL VERIFY WALL DIMENSIONS. GENERAL REQUIREMENTS: A. CONTRACTOR SHALL VERIFY CATALOG NUMBERS AND INSTALLATION REQUIREMENTS PRIOR TO ORDERING. NOTIFY ENGINEER OF ANY CONFLICTS WITH PROPOSED INSTALLATION. B. INSTALL PER MANUFACTURER'S INSTRUCTIONS. C. CONFIRM FINAL LOCATION WITH ARCHITECT AND OWNER PRIOR TO ROUGH-IN. D. VERIFY FINISH AND FLOORING TYPE PRIOR TO ORDERING. E. SAWCUT EXISTING CONCRETE FLOORS AS REQUIERD TO INSTALL NEW BOXES. FLOORBOX SCHEDULE NOTES: 1. FLOORBOX SHALL BE CONSIDERED EQUAL AS MANUFACTURED BY: WIREMOLD, HUBBELL. 2. PROVIDE WITH INTERNAL RJ DEVICE BRACKETS AND ALL OTHER MOUNTING HARDWARE AS REQUIRED. 3. PROVIDE CONDUIT FROM CONNECTOR ROUTED UNDERFLOOR, UP CONCEALED IN WALL, AND STUBBED TO ABOVE ACCESSIBLE CEILING SPACE. TERMINATE WITH INSULATING BUSHING. 4. COORDINATE FINISH AND COLOR WITH ARCHITECT PRIOR TO OREDERING. 5. PROVIDE L5-15 RECEPTACLE FOR SPECIALTY EQUIPMENT, FIELD VERIFY RECEPTACLE CONFIGURATION WITH TSA EQUIPMENT. 6. PROVIDE WITH BARE CONCRETE / TERRAZO RING # EFB45-CTR. GENERAL REQUIREMENTS: A. VERIFY VOLTAGE, AND PHASE WITH MECHANICAL CONTRACTOR AND APPROVED SHOP DRAWINGS PRIOR TO INSTALLATION. SCHEDULE NOTES: 1. MECHANICAL EQUIPMENT PROVIDED WITH INTEGRAL DISCONNECT. 2. PROVIDE 2#12,#12G,1/2"C. BETWEEN INDOOR AND OUTDOOR UNIT. MECHANICAL UNIT DERIVES POWER FROM AUXILIARY MECHANICAL EQUIPMENT. EQUIPMENT LISTED IN (). 3. PROVIDE 1/2"C. FOR CONTROL WIRING BETWEEN INDOOR AND OUTDOOR UNIT. ROUTE CONDUIT WITH REFRIGERANT PIPING. 4. PROVIDE VOLTAGE MATCHED ELECTRICAL CONNECTION TO MOTORIZED DAMPER ON EQUIPMENT. 5. CONNECT FAN DOWN STREAM OF ROOM OCCUPANCY SENSOR SO FAN OPERATES DURING OCCUPANCY. 6. CONNECT TO BRANCH CIRCUIT INDICATED ON FLOOR PLANS. 7. DISCONNECT SHIPPED LOOSE FROM EQUIPMENT, ELECTRICAL CONTRACTOR TO CONNECT TO EQUIPMENT AND BRANCH CIRCUIT TO DISCONNECT PROVIDED. 8. ROUTE CONDUITS CONCEALED AS BEST AS POSSIBLE IN EXISTING CEILING AREA. PAINT EXPOSED CONDUITS TO MATCH CEILING / WALL COLORS. TS S EXIT L 6" EXIT DOOR 6 4 STANDARD DOOR 1 DEVICES: 2 3 4 5 6 N O T E 4 DIMMER SWITCH F I R E F TEMPERATURE SENSORTHERMOSTAT NOTE 1 WALL SWITCH FLOOR C WALL BOX CR SCTC NOTES: ALIGN DEVICES VERTICALLY AND HORIZONTALLY WHEREVER POSSIBLE. NOT ALL DEVICES OR CONFIGURATIONS ARE DEPICTED ON THIS DETAIL. FOR ANY CONFIGURATIONS WITH FOUR OR MORE DEVICES, COORDINATE ARRANGEMENT WITH THE ENGINEER PRIOR TO ROUGH-IN. SEE FLOOR PLANS FOR INDIVIDUAL DOOR REQUIREMENTS. WHERE MULTIPLE SWITCHES OR WALL BOX DIMMERS ARE GANGED TOGETHER, ALIGN FIRST GANG WITH DEVICES ABOVE AND ADD DEVICES TO THE RIGHT AS REQUIRED. DIMENSIONS ARE TO BE MEASURED FROM OUTSIDE EDGE OF DOOR FRAME OR TRIM. WHERE SIDE LIGHT WINDOWS ARE PROVIDED, DIMENSIONS SHOULD BE MEASURED FROM OUTSIDE EDGE OF SIDE LIGHT WINDOW FRAME OR TRIM. ALL DEVICES SHALL BE LOCATED TO MAINTAIN ALL A.D.A. MOUNTING HEIGHT REQUIREMENTS AND SUCH THAT CENTER OF ADJACENT DEVICES ARE AT SAME ELEVATION (TYPICALLY 44" A.F.F. TO CENTER OF DEVICE). NOTIFY ENGINEER OF ANY CONFLICTS WITH THE PROPOSED INSTALLATION. WALL SWITCH, WALL OCCUPANCY SENSOR SWITCH, WALL BOX DIMMER SWITCH, OR ENTRY STATION THERMOSTAT, TEMPERATURE SENSOR, OR CARBON DIOXIDE SENSOR ROUGH-IN FIRE ALARM AUDIO/VISUAL INDICATING DEVICE FIRE ALARM PULL STATION ACCESS CONTROL CARD READER EXIT SIGN TV CONTROL SHADE CONTROL ACCESS CONTROL CARD READER WALL OCCUPANCY SENSOR SWITCH CARBON DIOXIDE SENSOR FIRE ALARM PULL STATION ENTRY STATION 3 1 NOTE 2 44 " U .N .O . 6" 2 CL CL CL 6" 3 CL 6" 6" 5 44 " U .N .O . LC NOTE 3 (TYPICAL) 1. 2. 3. 4. NOTE 3 (TYPICAL) 84 " 84 " 1 (XX-##) 3[a] 2[b] 2[b] 2[b] 2[b] 2[b] 2[b] 3[a]3[a] [a] (XX-##) [b] (XX-##) 1 [a] 4[a] 4[a]4 NL [a,b] [a] [b]LS1 LS2 LS3 PP PP PP [a] (XX-##) SUBSCRIPT "NL" DENOTES NIGHT LIGHT HATCHING INDICATES LUMINAIRE WITH INTEGRAL BATTERY OR CONNECTED TO EMERGENCY CIRCUIT CONNECT LUMINAIRES AND CONTROL DEVICE TO CIRCUIT INDICATED CONNECT LUMINAIRES TO LIGHTING CONTROL DEVICE WITH MATCHING SUBSCRIPT SEE LIGHTING CONTROL SEQUENCE OF OPERATIONS SEE LIGHTING CONTROL DEVICE SCHEDULE AND SPECIFICATIONS CONNECT LIGHTING CONTROL DEVICE TO LUMINAIRES IN ROOM UNLESS NOTED OTHERWISE NOTE: NOT ALL CONFIGURATIONS ARE SHOWN ON TYPICAL PLAN. m o e y rr Is s e n g I n e e r I n g I n c m e c h a n ic a l | e le c tr ic a l | te c h n o lo g y | c o m m is s io n in g 4 9 4 0 N o rt h 1 1 8 th S tr e e t O m a h a , N E 6 8 1 6 4 P : 4 0 2 .4 9 1 .4 1 4 4 w w w .m o rr is s e y e n g in e e ri n g .c o m M E I P R O J E C T # : E N G I N E E R S O ET A T S P R O F E RBENF A KSA L O N S I AL E EC ITR CAL ∆ ∆ TOBY J. E-12606 SAMUELSON SHEET NO. DATE PROJECT KEARNEY TERMINAL SEAL NO . RE VI SI ON S DA TE CIVIL ENGINEER DR AW N BY : DE SI GN ED BY : RE VI EW ED BY : QU AN TI TI ES CH EC KE D BY : ARCHITECT CONSULTANT K E A R N E Y R E G IO N A L A IR P O R T T E R M IN A L E X P A N S IO N K E A R N E Y , N E B R A S K A 2 0 3 7 1 07/29/2022 7/29/2022 E6.1 EL EC TR IC AL SC HE DU LE S LUMINAIRE SCHEDULE MARK DESCRIPTION MANUFACTURER CATALOG NUMBER LIGHT SOURCE ELECTRICAL FINISH MOUNTING ACCEPTABLE MANUFACTURERS REMARKSSPEC. CCT TYPE LOAD VOLTS 1 1x4 TROFFER LITHONIA EPANL 1x4 4000LM 80CRI 35K MIN10 ZT MVOLT 4,000 LM 3500K LED 37 W 120 V WHITE RECESSED/CEILING NOTE 1 1A 2x4 TROFFER LITHONIA EPANL 2X4 6000LM 80CRI 35K MIN10 ZT MVOLT 6,000 LM 3500K LED 50 W 120 V WHITE RECESSED/CEILING NOTE 1 2 2x4 TROFFER FOCAL POINT FEQ2 24 AC 4000LH 35K 1C UNV LD1 G1 WH 4,000 LM 3500K LED 33 W 120 V WHITE RECESSED/CEILING NOTE 1 3 2x4 TROFFER FOCAL POINT FEQ2 24 AC 6000LH 35K 1C UNV LD1 G1 WH 6,000 LM 3500K LED 47 W 120 V WHITE RECESSED/CEILING NOTE 1 4 ASYMMETRIC UPLIGHT BEGA 24 362 K35 WHT 3,727 LM 3500K LED 34 W 120 V WHITE SURFACE/WALL INSIGHT 5 PERIMETER WALLSLOT, GRAZE SELUX L10P 1C35 935 LW 4PM XX WH U DIM 1000 LM/FT 3500K LED 9 W/FT 120 V WHITE RECESSED AXIS, PRUDENTIAL NOTE 4 6 4' LED STRIPLIGHT LITHONIA ZL1D L48 SMR 5000LM FST MVOLT 35K 80CRI WH 5,000 LM 3500K LED 41 W 120 V WHITE SURFACE NOTE 1, LUMAX 7A 4' LED STRIPLIGHT LITHONIA ZL1D L48 SMR 5000LM FST MVOLT 35K 80CRI WH ZACVH M100 5,000 LM 3500K LED 41 W 120 V WHITE SUSPENDED NOTE 1, LUMAX 7B 8' LED STRIPLIGHT LITHONIA ZL1D L96 SMR 10000LM FST MVOLT 35K 80CRI WH ZACVH M100 10,000 LM 3500K LED 81 W 120 V WHITE SUSPENDED NOTE 1, LUMAX 8A 4" ROUND LED DOWNLIGHT GOTHAM EVO4 35/25 AR WD LD MVOLT GZ10 2,500 LM 3500K LED 26 W 120 V MATTE DIFFUSE RECESSED/CEILING NOTE 2 8B 4" ROUND LED DOWNLIGHT GOTHAM EVO4 35/25 AR MD LD MVOLT GZ10 2,500 LM 3500K LED 26 W 120 V MATTE DIFFUSE RECESSED/CEILING NOTE 2 9 LED WALLPACK LITHONIA WDGE P3 30K 80CRI VW MVOLT SRM DBLXD 3,000 LM 3000K LED 23 W 120 V BLACK SURFACE/WALL NOTE 1 10B 8' LED STRIPLIGHT, IP66 LITHONIA FEM L96 12000LM IMAFD WD MVOLT GZ10 35K 80CRI 12,000 LM 3500K LED 76 W 120 V WHITE SUSPENDED NOTE 1 11 20' WALLWASH PENDANT VODE 107-WG 01 20' 96" CC 48 2R25 AE 1 0 Z HO 35 WB 0 WH 0 1107 LM/FT 3500K LED 12 W/FT 120 V ALUMINUM SUSPENDED INSIGHT 12 10' DIRECT PENDANT LUMIUM TR1 CSD CR10' 35K SO UNV 10D SC MF MA 55 SW PSS 4 XX 765 LM/FT 3500K LED 8 W/FT 120 V ALUMINUM SUSPENDED INSIGHT 13 8' LINEAR LED WALLWASH SELUX L1R1 1C30 835 A2 TBS 8 WH U DIM 765 LM/FT 3500K LED 39 W 120 V WHITE RECESSED/CEILING AXIS, PRUDENTIAL X1 SINGLE FACE EXIT SIGN LITHONIA TLE 1 R FURN. W/ LUMINAIRE FURN. W/ LUMINAIRE LED 2 W 120 V ALUMINUM NOTE 3 NOTE 1, ISOLITE X2 DOUBLE FACE EXIT SIGN LITHONIA TLE 2 R FURN. W/ LUMINAIRE FURN. W/ LUMINAIRE LED 2 W 120 V ALUMINUM NOTE 3 NOTE 1, ISOLITE X3 SINGLE FACE EXIT SIGN LITHONIA EDGR 1 R FURN. W/ LUMINAIRE FURN. W/ LUMINAIRE LED 2 W 120 V ALUMINUM NOTE 3 NOTE 1, ISOLITE X4 SINGLE FACE EXIT SIGN CONCEALITE IX G R AC SD FURN. W/ LUMINAIRE FURN. W/ LUMINAIRE LED 2 W 120 V ALUMINUM NOTE 3 -- FLOORBOX SCHEDULE MARK DESCRIPTION MANUFACTURER MODEL COVER RECEPTACLE LOW VOLTAGE CONDUIT ACCEPTABLE MANUFACTURERS REMARKSSTYLE TOP FLANGE FINISH FBE4 4-GANG MULTI-SERVICE ON GRADE RECESSED FLOORBOX WIREMOLD EFB45S-OG EFB45 B T NOTE 4 (2) 5-20 (2) 1" NOTE 1 NOTE 2,3,6 FBE6A 6-GANG MULTI-SERVICE ON GRADE RECESSED FLOORBOX WIREMOLD EFB6S-OG EFB610 C TC NOTE 4 (1) 5-20, NOTE 5 (2) 1" NOTE 1 NOTE 2,3 FBE8A 8-GANG MULTI-SERVICE ON GRADE RECESSED FLOORBOX WIREMOLD EFB8S-OG EFB610 C TC BLACK (4) 5-20, NOTE 6 (2) 1" NOTE 1 NOTE 2,3 LIGHTING CONTROL DEVICE SCHEDULE SYMBOL TAG MANUFACTURER CATALOG NUMBER DESCRIPTION GFX ACUITY CONTROLS NLIGHT nPOD TOUCH LIGHTING CONTROL NETWORK TOUCH SCREEN GRAPHIC WALLPOD 1P ACUITY CONTROLS NLIGHT nPODMA LIGHTING CONTROL NETWORK ENTRY STATION WITH ON AND OFF PUSH BUTTONS 1PD ACUITY CONTROLS NLIGHT nPODMA DX LIGHTING CONTROL NETWORK ENTRY STATION WITH ON AND OFF PUSH BUTTONS AND RAISE/LOWER DIMMING CONTROL nE ACUITY CONTROLS NLIGHT nCM PDT 10 EXTENDED RANGE LOW VOLTAGE CEILING SENSOR CONNECTED TO LIGHTING CONTROL NETWORK n ACUITY CONTROLS NLIGHT nIO PC KIT OUTDOOR PHOTOCELL KIT CONNECTED TO LIGHTING CONTROL NETWORK 2 ACUITY CONTROLS NLIGHT nPANEL 2 480 LIGHTING CONTROL NETWORK PANEL WITH TWO DUAL-POLE RELAYS (208/240/480V) AND TWO 0-10V DIMMING OUTPUTS n,D ACUITY CONTROLS NLIGHT nPP16 D LIGHTING CONTROL NETWORK 16A POWER PACK WITH 0-10V DIMMING em,D ACUITY CONTROLS NLIGHT nPP16 D ER LIGHTING CONTROL NETWORK 16A UL924 EMERGENCY POWER PACK WITH 0-10V DIMMING em ACUITY CONTROLS NLIGHT nPP16 ER LIGHTING CONTROL NETWORK 16A UL924 EMERGENCY POWER PACK MECHANICAL CONNECTION SCHEDULE Mark VOLTAGE PHASE DISCONNECT BREAKER WIRE AND CONDUIT Panel Circuit Number REMARKS AC-108 208 V 1 2P TOGGLE - 2#12,#12G,1/2"C LP1 37,39 NOTES 2,3 (ACCU-108) AC-118 208 V 1 2P TOGGLE - 2#12,#12G,1/2"C LP2 31,33 NOTES 2,3 (ACCU-118) AC-124 208 V 1 2P TOGGLE - 2#12,#12G,1/2"C T 19,21 NOTES 2,3 (ACCU-124) ACCU-108 208 V 1 30/2/NF/3R 25/2 2#10,#10G,3/4"C LP1 37,39 ACCU-118 208 V 1 30/2/NF/3R 25/2 2#10,#10G,3/4"C LP2 31,33 ACCU-124 208 V 1 30/2/NF/3R 25/2 2#10,#10G,3/4"C T 19,21 EF-116 115 V 1 NOTE 1 20/1 2#12,#12G,1/2"C LP2 36 NOTE 5 EF-125 115 V 1 NOTE 1 20/1 2#12,#12G,1/2"C T 39 EF-136 115 V 1 NOTE 1 20/1 2#12,#12G,1/2"C LP2 36 NOTE 5 EH-101A 208 V 1 2P TOGGLE 20/2 2#12,#12G,1/2"C LP3 13,15 NOTE 8 EH-101B 208 V 1 2P TOGGLE 20/2 2#12,#12G,1/2"C LP3 17,19 NOTE 8 EUH-122 208 V 1 NOTE 1 20/2 2#12,#12G,1/2"C T 58,60 NOTE 7 EWH-103 208 V 1 NOTE 1 30/2 2#10,#10G,3/4"C LP2 37,39 EWH-126 208 V 1 NOTE 1 30/2 2#10,#10G,3/4"C T 52,54 EWH-129 120 V 1 NOTE 1 20/1 2#12,#12G,1/2"C T 56 GFUH-104 120 V 1 2P TOGGLE 20/1 2#12,#12G,1/2"C LP3 11 GFUH-119 120 V 1 2P TOGGLE 20/1 2#12,#12G,1/2"C LP2 35 GFUH-M150 120 V 1 2P TOGGLE 20/1 2#12,#12G,1/2"C NOTE 6 IEWH-1 208 V 1 LOCKABLE BREAKER 50/2 2#6,#10G,1"C T 43,45 RTU-121 208 V 3 NOTE 1 40/3 3#8,#8N,#10G,1"C T 40,42,44 RTU-123 208 V 3 NOTE 1 35/3 3#8,#8N,#10G,1"C T 46,48,50 RTU-131 208 V 3 NOTE 1 35/3 3#8,#8N,#10G,1"C LP2 25,27,29 WS-1 120 V 1 CORD & PLUG - - SCALE: NOT TO SCALEE6.1 1 DEVICE ALIGNMENT DETAIL SCALE: NOT TO SCALEE6.1 2 TYPICAL LIGHTING AND CONTROL PLAN PROVIDE FAST-TRANSFER, PURE SINE WAVE EMERGENCY LIGHTING INVERTER WITH QUANTITY OF OUTPUT BREAKERS INDICATED BY EVENLITE, DUAL LITE, OR ISOLITE. PROVIDE WITH ADEQUATE CAPACITY TO ACCOMMODATE LED LOADS INDICATED IN SCHEDULE FOR 90 MINUTE OPERATION. MANUFACTURER TO DETERMINE CAPACITY BASED ON ACTUAL PRODUCT DATA SUBMITTED DURING SHOP DRAWINGS AND OVERLOAD CAPACITY OF INVERTER. PROVIDE WITH SELF-TEST / SELF-DIAGNOSTICS OPTION AND MINIMUM 2 YEAR WARRANTY. FOR INVERTERS WITH MULTIPLE OUTPUT BREAKERS, PROVIDE INVERTER WITH SURGE SUPPRESSION. Notes: 472 W 1 LTG - NORTH EGRESS 472 W 120 V OB# DESCRIPTION LOAD VOLTAGE NOTES Location: OFFICE 108 Panel: LP1 Inverter: INV-1 Voltage: 120V INVERTER SCHEDULE PROVIDE FAST-TRANSFER, PURE SINE WAVE EMERGENCY LIGHTING INVERTER WITH QUANTITY OF OUTPUT BREAKERS INDICATED BY EVENLITE, DUAL LITE, OR ISOLITE. PROVIDE WITH ADEQUATE CAPACITY TO ACCOMMODATE LED LOADS INDICATED IN SCHEDULE FOR 90 MINUTE OPERATION. MANUFACTURER TO DETERMINE CAPACITY BASED ON ACTUAL PRODUCT DATA SUBMITTED DURING SHOP DRAWINGS AND OVERLOAD CAPACITY OF INVERTER. PROVIDE WITH SELF-TEST / SELF-DIAGNOSTICS OPTION AND MINIMUM 2 YEAR WARRANTY. FOR INVERTERS WITH MULTIPLE OUTPUT BREAKERS, PROVIDE INVERTER WITH SURGE SUPPRESSION. Notes: 663 W 1 LTG - SOUTH EGRESS 663 W 120 V OB# DESCRIPTION LOAD VOLTAGE NOTES Location: MECHANICAL 122 Panel: T Inverter: INV-2 Voltage: 120V INVERTER SCHEDULE 1 Ad de nd um N o. 1 8/ 24 /2 02 2 2 Ad dn eu dm N o. 2 8/ 26 /2 02 2 1 1 2 TERMINAL EXPANSION KEARNEY REGIONAL AIRPORT (EAR) KEARNEY, NEBRASKA AIP 3-31-0045-036 (CARES) ADDENDUM NO. 2 Attachment No. 3 Plan Holders List AIRPORT NAME: Kearney Regional Airport (EAR) ASSOCIATED CITY, STATE: Kearney, NE PROJECT NAME: Terminal Expansion Plans & Specifications: Contractor Add #1 City State Zip Phone # Fax # View Plans & Specs Received "Yes" Date Sent No. 01 No. 02 Email Address Kearney Regional Airport (Office of The Airport Manager) Office of the Airport Manager Kearney NE 68848 308-234-2318 Yes JLynaugh@kearneygov.org City of Kearney (City Hall) 18 East 22nd St. Kearney NE 68848 308-233-3216 Yes Yes 8/25 LBrandt@kearneygov.org FAA 901 Locust St., ACE-600, Room 364 Kansas City MO 64106 816-329-2630 816-329-2610 Yes Steve.Whitton@faa.gov Lincoln Builders Bureau 5910 S. 58th St. Suite C Lincoln NE 68516 402-421-8332 402-421-8334 Yes builders@cornhusker.net Omaha Builders Exchange 4159 S 94th St Omaha NE 68127 402-991-6906 402-884-7055 Yes lisa.shockey@omahaplanroom.com Dodge Reports (McGraw Hill) 830 3rd Avenue, 6th floor New York NY 10022 800-393-6343 402-496-7410 Yes support@construction.com Construct Connect 323-602-5079 Yes desirree.sibala@constructconnect.com Nebraska Department of Aeronautics 3431 Aviation Road, Suite 150 Lincoln NE 68524 402-471-2371 Yes anna.lannin@nebraska.gov RMV Construction 1515 E 11th St Kearney NE 68847 308-240-0144 Yes 8/10 8/12 @9:17am 8/10/2022 ken@rmvconst.com Lacy Construction Company 4586 Gold Core Drive, Suite C Grand Island NE 68801 308-384-2866 Yes 8/11 ashkay.chavan@lacygc.com Watts Electric Company 13351 Dovers Street Waverly NE 68462 402-786-2270 Yes 8/15 projects@gowatts.com CSI Services Inc. 1320 East 8th Street North Platte NE 308-530-3761 Yes 8/15 jordan@csitraffic.com Beckenhauer Construction Inc. 1901 Riverside Blvd Norfolk NE 687010 402-371-5363 Yes 8/15 8/18/2022 8/17/2022 joeb@beckenhauerconstruction.com MCL Construction 4111 4th Avenue, Ste 32 Kearney NE 68845 402-290-6809 Yes 8/15 zach.wetzel@mclconstruction.com Central Contracting 4407 First Ave Place Kearney NE 68848 308-234-2421 Yes 8/15 sbeall@centralcontracting.net Sampson Construction 5825 S 14th St Lincoln NE 68512 402-434-5420 Yes 8/15 8/16 @ 9:57am 8/15/2022 estimating@sampson-construction.com Midlands Contracting Inc. 308-237-7979 Yes 8/16 susan@midlandscontracting.com Kidwell 402-473-7760 Yes 8/16 tjonas@kidwellinc.com R&M Steel PO Box 580 Caldwell ID 83606 208-454-1800 Yes 8/16 kerby@rmsteel.com Venetian Cast Stone 2171 Magnum Circle Lincoln NE 68522 402-470-0020 Yes 8/16 zachc@venetiancs.com Pruss Excavation Yes 8/16 annettee@prussexcavation.com Lovci Construction & Fabrication LLC 402-942-1698 Yes 8/16 codie@lovciconstruction.com AMAX Contracting, Inc. 3509 Antelope Ave Kearney NE 68847 308-236-5667 Yes 8/17 amax.gail@gmail.com Verne Simmons Company 8445 Madison Street Omaha NE 68127 402-827-8085 402-592-0853 Yes 8/18 briand@v-s-c.com Horizon Boring & Tunneling Co. PO Box 429 Exeter NE 68351 402-266-5347 Yes 8/19 Yes 8/26 horizontalboring@hbttrenchless.com Five Star Airport Alliance 1630 South 4800 West Suite D Salt Lake City UT 84104 801-69-1602 Yes 8/22 Danielle.Coombs@fivestaraa.com Access Electrical Systems Inc 701 W. 4th Street Grand Island NE 68801 308-390-6274 Yes 8/26 john@accesselectrialsystemsinc.com Bauer Infrastructure LLC Yes 8/30 truhge@bauerinfrastructure.com ADDENDUMS DATE ADDENDUM MAILED No. 01 August 25, 2022 No. 02 August 30, 2022 No. 03 --- No. 04 --- No. 05 --- Official Proposal Form Addendum Confirm AIP No.: 3-31-0045-036, CARES Date of Bid Opening: Time of Bid Opening Benesch Job Number: 9/1/2022 2:00 PM 112045.02 8/30/2022 Page 1 of 1 Benesch PHL

City of Kearney, NE 68847, United StatesLocation

Address: City of Kearney, NE 68847, United States

Country : United StatesState : Nebraska

You may also like

Adirondack Regional Airport (SLK) -- Airport Terminal Revitalization

Due: 14 May, 2024 (in 24 days)Agency: Passero Associates Engineering Archtecture

TSA RDU TERMINAL 1 REMODEL RALEIGH DURHAM INTERNATIONAL AIRPORT, RALEIGH, NC 27604-3889

Due: 30 Apr, 2024 (in 11 days)Agency: PUBLIC BUILDINGS SERVICE